Short answer: Title 24 insulation requirements have two layers. Mandatory minimums apply in every climate zone: framed walls need at least R-15 in 2×4 framing or R-21 in 2×6 framing. Prescriptive values then vary by zone. Under the 2025 code, a vented attic calls for R-38 in Climate Zones 1 and 8–16 and R-30 in Zones 2–7, and raised floors call for R-19 everywhere. Most new homes and ADUs use the performance method instead, so your Title 24 report confirms the values your project must meet.
Need a Title 24 report for your permit?
ADU from $199 · Single-family from $245 · Multifamily from $345 per building. Permit-ready PDF in 2–3 business days, CHEERS-registered where required, two revisions included.
How Title 24 Insulation Requirements Work
The Energy Code treats insulation in three ways, and all three show up on a typical report:
- Mandatory measures are minimums that apply whatever compliance method you use, such as the wall insulation limits in §150.0(c).
- Prescriptive requirements are the zone-by-zone values in Table 150.1-A. Meeting every prescriptive requirement is one way to comply without an energy model.
- The performance method models the whole building in CEC-approved software and compares it with a standard design built to the prescriptive values. A design can use less insulation in one place if it makes up the difference elsewhere, but never less than the mandatory minimums.
For how insulation fits with windows, HVAC and the rest of the building, see Title 24 requirements. For how modeling trades features off, see Title 24 calculations.
Insulation Requirements by Climate Zone (2025 Prescriptive Values)
These values come from Table 150.1-A of the 2025 Standards for single-family buildings, as published on Energy Code Ace. They are prescriptive: the levels a design must meet if it does not use the performance method. The full table includes conditions and other components not shown here.
| Climate zone | Vented attic ceiling (Option C) | Below-deck insulation (Option B) | Framed wall, max U-factor |
|---|---|---|---|
| 1 | R-38 | None listed | U-0.048 |
| 2 | R-30 | None listed | U-0.048 |
| 3 | R-30 | None listed | U-0.048 |
| 4 | R-30 | R-19 | U-0.048 |
| 5 | R-30 | None listed | U-0.048 |
| 6 | R-30 | None listed | U-0.065 |
| 7 | R-30 | None listed | U-0.065 |
| 8 | R-38 | R-19 | U-0.048 |
| 9 | R-38 | R-19 | U-0.048 |
| 10 | R-38 | R-19 | U-0.048 |
| 11 | R-38 | R-19 | U-0.048 |
| 12 | R-38 | R-19 | U-0.048 |
| 13 | R-38 | R-19 | U-0.048 |
| 14 | R-38 | R-19 | U-0.048 |
| 15 | R-38 | R-19 | U-0.048 |
| 16 | R-38 | R-19 | U-0.048 |
Two items are the same in every zone: raised floors at U-0.037 (R-19), and Quality Insulation Installation. Option C insulates the ceiling of a vented attic; Option B adds insulation below the roof deck. Which option suits a home depends on its roof and attic design, and your report shows the one modeled. Several of these values changed in this cycle; see 2025 Title 24 changes.
Mandatory Wall Insulation Minimums
Under §150.0(c), framed walls must meet a maximum U-factor of 0.095 for 2×4 framing (at least R-15 at 16 inches on center) or 0.069 for 2×6 framing (at least R-21). A lower U-factor means less heat flow, so it is the stricter number. The prescriptive wall value in the table, U-0.048 in most zones and U-0.065 in Zones 6 and 7, is lower than either mandatory limit. A wall built only to the mandatory minimum therefore does not meet the prescriptive value on its own. Under the performance method, a wall between the two can still work if other features compensate.
Attics, Cathedral Ceilings and Ducts
The 2025 code sets the prescriptive vented-attic ceiling value at R-38 in Climate Zones 1 and 8–16 and R-30 in Zones 2–7 (§150.1(c)1Aiii). Cathedral ceilings, where the ceiling follows the roof line, call for R-38 with no radiant barrier in all zones. Ducts in unvented attics may be insulated to R-4.2 when other requirements are met (§150.0(m)1Bi).
Ceiling insulation also matters on a re-roof. Where a steep-slope re-roof needs a cool roof, at least R-38 ceiling insulation is one of the accepted alternatives; see Title 24 re-roof requirements.
Quality Insulation Installation (QII)
Table 150.1-A lists QII as a prescriptive requirement in every climate zone. QII is field-verified: an ECC-Rater, still often called a HERS rater, checks the insulation and air sealing while they are visible, before walls and ceilings are closed. Plan the inspection into the construction schedule, because work covered too early may have to be opened up. Your CF1R shows whether QII applies to your design; see when a rater is needed.
Prescriptive or Performance: Which Values Apply to You
Most new homes and ADUs comply through the performance method, so the values on your report may differ from the table. A little more attic insulation can offset a wall, or better windows can offset a ceiling. Additions and alterations are handled differently: an addition can be modeled on its own or with the existing home, and altered components follow their own rules. Your report lists the insulation levels your plans must show.
- ADU energy compliance: how detached, attached and converted ADUs are treated.
- Home addition insulation: new walls, ceilings and floors in an addition.
- Garage conversion insulation: bringing a garage into the living space.
How to Find Your Zone's Insulation Values
Your climate zone is set by the project address, not the city name alone. Look it up on our California climate zones page, then open the guide for your zone, for example Climate Zone 3, Climate Zone 9, Climate Zone 12 or Climate Zone 16. When you order a report, we confirm the zone from the address on your plans.
Frequently Asked Questions
What R-value do I need in my attic in California?
Under the 2025 prescriptive values, a vented attic needs R-38 in Climate Zones 1 and 8–16 and R-30 in Zones 2–7. A performance design may use a different value, and your report states the one that applies.
Do I have to upgrade insulation in my existing home?
Not because the code changed. Insulation requirements apply to new construction, additions and the parts of a home you alter. Some alterations, such as certain re-roofs, bring in insulation-related options, and your building department decides what the permit covers.
Can I use less insulation than the table shows?
Yes, under the performance method, if other features make up the difference and the mandatory minimums are still met. Under the prescriptive method, each value must be met as listed.
Is QII the same as the building inspection?
No. The building inspector checks the work against the approved plans. QII is a separate field verification by an independent ECC-Rater, and the results are registered with the data registry.