Short answer: A re-roof on a California single-family home can trigger Title 24 cool roof requirements, generally when about half or more of the roof is replaced. Under the 2025 Energy Code, steep-slope roofs in Climate Zones 4 and 8–15 need a CRRC-rated product with an aged solar reflectance of at least 0.20 and a thermal emittance of at least 0.75, or an SRI of at least 16. Low-slope roofs in Zones 4 and 6–15 need 0.63 and 0.75, or an SRI of at least 75. Several exceptions apply, and your building department confirms what your permit needs.
Need a Title 24 report for your permit?
ADU from $199 · Single-family from $245 · Multifamily from $345 per building. Permit-ready PDF in 2–3 business days, CHEERS-registered where required, two revisions included.
When Does a Re-Roof Trigger Title 24?
The Energy Code treats re-roofing, meaning replacing, recovering or recoating a roof, as an alteration covered by §150.2(b)1I. The cool roof rules apply generally when about half or more of the roof is replaced. Your building department confirms whether your project reaches that point and what it needs with the permit.
Once the rules apply, the requirement depends on your climate zone and roof slope. In zones not listed below, the 2025 Energy Code sets no cool roof requirement for single-family re-roofs, although some cities adopt stricter local rules. For other common triggers, see when Title 24 is required.
Cool Roof Requirements in California by Roof Slope
Steep-slope roofs are pitched roofs, typically covered with shingles or tile. Low-slope roofs are nearly flat, typically covered with membranes or coatings. The code defines each slope category precisely, and your roofer or report confirms which one applies.
| Roof type | Climate zones | Aged solar reflectance | Thermal emittance | Or SRI |
|---|---|---|---|---|
| Steep slope | 4, 8–15 | 0.20 or higher | 0.75 or higher | 16 or higher |
| Low slope | 4, 6–15 | 0.63 or higher | 0.75 or higher | 75 or higher |
| Climate zone | Steep-slope re-roof | Low-slope re-roof |
|---|---|---|
| 1, 2, 3, 5, 16 | No cool roof requirement | No cool roof requirement |
| 4 | Cool roof required | Cool roof required |
| 6, 7 | No cool roof requirement | Cool roof required |
| 8–15 | Cool roof required | Cool roof required |
Source: the Cool Roof Rating Council's 2025 Energy Code summary chart (December 4, 2025). Aged solar reflectance measures how much sunlight a roof reflects after weathering. Thermal emittance measures how readily it releases the heat it absorbs. The Solar Reflectance Index (SRI) combines the two into one number, so a product can qualify with either the reflectance and emittance pair or the SRI. Check your zone with the climate zone lookup.
Exceptions and Equivalent Options
Steep-slope roofs
Instead of a cool roof product, the CRRC chart treats any of these as equivalent:
- A ceiling U-factor of 0.025 or less, or at least R-38 ceiling insulation.
- An attic radiant barrier that meets §150.1(c)2, not installed directly above spaced sheathing.
- In Climate Zones 2, 4, 9, 10, 12 and 14, no ducts in the attic.
- Continuous insulation of R-2 or more above or below the roof deck.
For attic insulation values by zone, see Title 24 insulation requirements.
Low-slope roofs
A low-slope re-roof can meet the requirement with roof-deck insulation under Table 150.2-B instead of a reflective surface. For example, there is no reflectance requirement with R-10 continuous deck insulation in Climate Zones 6 and 7, or R-24 in Zones 4 and 8–15.
Always exempt
Roof area under building-integrated photovoltaic or solar thermal panels is exempt, as are roof constructions weighing at least 25 lb/ft². Some tile or ballasted roofs may reach that weight; confirm the installed weight with your roofer. If solar is part of your plans, see Title 24 solar and battery requirements.
CRRC Ratings and Product Labels
To take credit as a cool roof, a product must be rated and labeled by the Cool Roof Rating Council (CRRC) under §10-113. Unrated products are assigned default values: 0.08 reflectance and 0.75 emittance for asphalt shingles, and 0.10 and 0.75 for other products. Both defaults fall below the 0.20 steep-slope minimum, so where a cool roof is required, an unrated product only works together with one of the exceptions above.
Ask your roofing supplier for the CRRC rating of the exact product and color, check that the aged values (not only the initial ones) meet the minimum, and keep the label or product data for the inspector.
Documentation for a Re-Roof Permit
Most re-roofs that need Title 24 paperwork use a prescriptive alteration form rather than a full energy model. For 2025 permits, building departments use a re-roof form such as the CF1R-ALT-01-E, which asks for the product's rated values or the exception used. Form names can change between code cycles, and some departments use their own versions. For how compliance forms are organized, see what a CF1R is.
When the re-roof is part of a larger permit, such as an addition, an ADU or a remodel that also changes windows or HVAC, the roof is usually included in the project's Title 24 report. Title24Comply prepares residential Title 24 reports from your plans; see pricing to order.
Cool Roofs on New Homes
New construction follows different values. Table 150.1-A of the 2025 Standards lists a prescriptive cool roof for new single-family homes with steep-slope roofs in Climate Zones 10–15 (aged solar reflectance 0.20 and thermal emittance 0.75, or SRI 16) and low-slope roofs in Zones 13 and 15 (0.63 and 0.75, or SRI 75). Because most new homes use the performance method, the roof can be traded against other features. See new construction Title 24 and the other 2025 Title 24 changes.
Frequently Asked Questions
Does a small roof repair need Title 24?
Usually not. The cool roof rules apply generally when about half or more of the roof is replaced, and your building department makes the call for your permit.
Does a cool roof have to be white?
No. The requirement is a rated performance level, not a color. Check the CRRC rating of the specific product and color you plan to use.
Is my tile roof exempt?
Roof constructions weighing at least 25 lb/ft² are exempt. Whether your tile roof qualifies depends on its installed weight, so confirm with your roofer or building department.
Can added attic insulation replace a cool roof?
For steep-slope re-roofs, yes: at least R-38 ceiling insulation, or a ceiling U-factor of 0.025 or less, is treated as equivalent. Low-slope roofs use the roof-deck insulation levels in Table 150.2-B.
Can my city require more than the state code?
Yes. Some cities adopt stricter local cool roof rules, so check with your building department before you order materials.